• Condition:  Dryer Master has detected the outlet moisture sensor indicates the outgoing grain has reached a high or low moisture level reaching the “warning” status.
  • Alarm Action Taken: WARNING ONLY
  • Component: Dryer Master Moisture Sensor.
  • Location: Normally mounted in the Dryer Master sampler box located somewhere either directly under the dryer or in the discharge grain stream prior to going to the storage bin, usually between the outlet of the reclaim conveyor and the inlet to the dry grain leg.

Tech tip: (Value is set in the “Dryer Master Alarm Settings” screen)

This alarm indicates a “warning” moisture condition of the outgoing grain from the dryer. If this alarm appears, proceed to the “Dryer Master Alarm Settings” screen to determine if the condition is warning high or warning low based on the current reading and the alarm values that have been set.

(After acknowledging the alarm, this alarm can be temporarily silenced by changing the warning moisture high or warning moisture low setting to take the dryer out of the alarm condition. This will provide time to investigate the cause of the alarm.)

Tools Required for Service:

  • Phillips screwdriver (to remove cover)
  • ½” wrench (to remove sensor from dryer)
  • Channel Lock (to loosen sealtite fitting)
  • Wire cutters/strippers (if replacing sensor)

Potential Causes of this Alarm Condition:

  • Blockage obstructing the grain from entering the sampler box
  • Sampler box motor faulty not moving grain
  • Warning High Alarm setpoint too low
  • Warning Low Alarm setpoint too high